SEER2 Energy Savings Calculator

Look up the DOE minimum SEER2 for new systems in your state, then compare yearly cooling costs at two ratings using your own electricity price.

SEER2 minimums and savings

Minimum for new systems: Split system air conditioner, under 45,000 Btu/hr

13.4SEER2 minimum (national standard)

Standards: 10 CFR 430.32, checked 2026-10-05. EIA reference prices: January to July 2026, released September 24, 2026.

SEER2 is the efficiency rating on central air conditioners and heat pumps made since January 1, 2023. A higher number means less electricity for the same cooling. The calculator does two things. First, it shows the federal minimum for the system type in your state, because split system air conditioners installed in the Southeast and Southwest must meet a higher level than in the rest of the country. Second, it estimates yearly cooling electricity and cost at your current rating and at a new rating, using your system size, your cooling hours, and your electricity price. Nothing is filled in for you except the EIA price, and only when you ask for it.

Worked example

Example inputs chosen to show the arithmetic, not typical values: a 36,000 Btu/h system running 1,000 hours a year, at the U.S. average EIA residential price for January to July 2026 (18.19 cents per kWh).

36,000 Btu/h x 1,000 hours
SystemkWh per yearCost per year
Minimum split system, SEER2 13.42,687$488.69
Higher efficiency, SEER2 16.02,250$409.28
Difference437$79.41

How it works

The 2024 edition of the Code of Federal Regulations defines SEER2 as "the total heat removed from the conditioned space during the annual cooling season, expressed in Btu's, divided by the total electrical energy consumed by the central air conditioner or heat pump during the same season, expressed in watt-hours" (10 CFR part 430, subpart B, appendix M1). The older SEER in appendix M is defined the same way under the earlier test. Turning the ratio around gives the formula:

kWh per year = capacity (Btu/h) x cooling hours per year / (SEER2 x 1,000)
Cost per year = kWh per year x price (cents per kWh) / 100
Savings = cost at the current SEER2 - cost at the new SEER2

Cooling hours are the hours your system would run at full capacity over a year. That number depends on your climate, house, and thermostat, so the calculator asks for it rather than assuming one.

DOE minimum efficiency standards

National minimums, products made on or after January 1, 2023 (10 CFR 430.32(c)(5))
Product classSEER2HSPF2
Split system air conditioner, under 45,000 Btu/hr13.4n/a
Split system air conditioner, 45,000 Btu/hr or more13.4n/a
Split system heat pump14.37.5
Single-package air conditioner13.4n/a
Single-package heat pump13.46.7
Small-duct, high-velocity system126.1
Space-constrained air conditioner11.7n/a
Space-constrained heat pump11.96.3
Regional minimums for air conditioners installed on or after January 1, 2023 (10 CFR 430.32(c)(6))
Product classSoutheast SEER2Southwest SEER2Southwest EER2
Split system air conditioner, under 45,000 Btu/hr14.314.311.7 or 9.8
Split system air conditioner, 45,000 Btu/hr or more13.813.811.2 or 9.8
Single-package air conditionernational levelnational level10.6

EER2 in the Southwest: "The 11.7 EER2 standard applies to products with a certified SEER2 less than 15.2," and 9.8 applies at 15.2 or higher (11.2 and 9.8 for the larger class). "Any model of outdoor unit that has a certified combination with a rating below the applicable standard level(s) for a region cannot be installed in that region."

Southeast: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana, Maryland, Mississippi, North Carolina, Oklahoma, Puerto Rico, South Carolina, Tennessee, Texas, Virginia, the District of Columbia, and the U.S. territories. Southwest: Arizona, California, Nevada, and New Mexico. Everywhere else, the national level applies.

EIA reference electricity prices

Reference only: average residential price by state from the U.S. Energy Information Administration, Electric Power Monthly, released September 24, 2026. Your own rate may differ. U.S. average: 18.19 cents per kWh for January to July 2026.

Residential average price, cents per kWh
StateJanuary to July 2026July 2026
Alabama16.5416.40
Alaska27.0928.83
Arizona15.4415.38
Arkansas13.6114.33
California33.2533.61
Colorado16.7217.00
Connecticut27.9724.16
Delaware17.8618.48
District of Columbia24.6625.21
Florida15.3015.03
Georgia15.4016.27
Hawaii46.2848.00
Idaho12.9613.73
Illinois19.2219.22
Indiana17.0416.73
Iowa14.2015.99
Kansas15.2115.27
Kentucky14.2713.81
Louisiana13.3512.72
Maine29.9932.41
Maryland21.3021.41
Massachusetts30.1430.49
Michigan21.5323.05
Minnesota16.2517.45
Mississippi15.1914.54
Missouri13.9616.09
Montana13.9514.99
Nebraska12.9013.78
Nevada13.5312.77
New Hampshire26.7926.60
New Jersey23.9825.19
New Mexico15.0816.09
New York29.3829.90
North Carolina14.9415.16
North Dakota12.3613.41
Ohio18.7019.45
Oklahoma13.5814.35
Oregon15.4015.97
Pennsylvania21.0421.72
Rhode Island29.2228.29
South Carolina15.9315.47
South Dakota14.5015.37
Tennessee13.8713.71
Texas16.0615.88
Utah13.1613.12
Vermont23.9523.75
Virginia16.8317.55
Washington14.4014.71
West Virginia15.4715.78
Wisconsin19.0019.06
Wyoming13.9514.36

Frequently asked questions

What is the minimum SEER2 rating in 2026?

For central air conditioners and heat pumps made on or after January 1, 2023, 10 CFR 430.32 sets 13.4 SEER2 for split system air conditioners and 14.3 for split heat pumps nationally. Split system air conditioners installed in the Southeast or Southwest need 14.3 SEER2 below 45,000 Btu/hr and 13.8 at 45,000 Btu/hr or more.

Which states are in the Southeast and Southwest regions?

Under 10 CFR 430.32(c)(6), the Southeast includes Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana, Maryland, Mississippi, North Carolina, Oklahoma, Puerto Rico, South Carolina, Tennessee, Texas, Virginia, the District of Columbia, and the U.S. territories. The Southwest is Arizona, California, Nevada, and New Mexico.

How do you calculate savings from a higher SEER2?

SEER is the heat removed in Btu divided by the electricity used in watt-hours over the cooling season. So yearly kWh = capacity (Btu/h) x cooling hours / (SEER2 x 1,000), and yearly cost = kWh x your price per kWh. Run it at both ratings and subtract.

Can I compare an old SEER rating with a new SEER2 rating?

Not directly. The rules say SEER is determined in accordance with appendix M and SEER2 in accordance with appendix M1 to 10 CFR part 430, subpart B, which are different test procedures. Use SEER2 figures for both systems when you can.

What electricity price should I use?

Use the price per kWh from your bill. If you do not have it, the calculator can fill in the EIA residential average for your state for January to July 2026 (Electric Power Monthly Table 5.6.B, released September 24, 2026).

More HVAC tools

Sources

  1. eCFR: 10 CFR 430.32, Energy and water conservation standards.
  2. eCFR: 10 CFR part 430, subpart B, appendix M (SEER definition).
  3. Code of Federal Regulations, 2024 edition (govinfo): 10 CFR part 430, subpart B, appendix M1.
  4. eCFR: 10 CFR part 430, subpart B, appendix M1.
  5. EIA Electric Power Monthly, Table 5.6.B.